Modbus register map

There is no fixed register table in this product, and that is deliberate. The display has a block of registers, and you decide what lives where: each variable you configure takes a slot in that block. Your PLC reads and writes those slots like any other Modbus registers. This page describes the model, so you can size and plan before ordering.

How addresses work

Three areas are the same physical block of registers, seen from three directions:

Variable valuesWhere the display reads the numbers and text it renders
Modbus slave windowWhat your PLC reads/writes — a straight 1:1 map of the same addresses
Master polling imageWhere values land when the panel polls a PLC as master

The slave window is an identity mapping: protocol address 0x0000 is register 0, 0x0001 is register 1, and so on. No offset, no translation table to maintain.

Register space per model

ModelControl cardRegister spaceMax variables per configuration
K1CH579128 registers (0–127)32
K2ESP32128 registers (0–127)128
K3ECP51024 registers (0–1023)64

Register space and variable count are independent: 64 variables can be spread across any addresses in the 0–1023 range. Confirm the figures for your exact model in the sheet supplied with the unit.

Variable types, and how many registers each takes

CodeTypeRegisters usedEncoding
0Decimal integer1Unsigned 16-bit raw value. Displayed as value / 10^dec.
1Long integer232-bit unsigned, low word first.
2Single-precision float2IEEE-754 float32 bit pattern, low word first. Displayed as float / 10^dec.
3Raw textN (as configured)Byte string, high byte first. GB2312; plain ASCII is a subset, so English text passes through unchanged. Trailing zero bytes are discarded.
4Preset string index1The register holds the index (0-based) of an entry in the preset string list.

Text never participates in threshold comparisons — the register holds bytes, not a number. Types 0, 1, 2 and 4 do, and for types 0 and 1 the comparison uses the raw register value.

Byte order — three conventions coexist

This is where most integrations go wrong, so it is worth stating explicitly rather than leaving to a datasheet footnote.

WhatOrder
16-bit values inside the PDUBig-endian (high byte first) — standard Modbus
32-bit values (long, float)Low word first across the two registers
Text bytesHigh byte first, so the byte order on the wire is the GB2312 byte order
RTU frame CRCLow byte first

Reading a 32-bit value as big-endian is the single most common mistake: the number comes out roughly 65536 times too large, or nonsense. Write a test value of 1 and read the two registers back before trusting any 32-bit mapping.

Function codes

CodeFunctionNotes
03Read holding registersStandard register access
04Read input registersSupported; the window is the same block
06Write single register
16Write multiple registersUse this for text and for 32-bit values so the pair is written in one transaction

Exception responses returned:

Assigning addresses

Two modes, and they can be mixed in one configuration.

ExplicitYou set the register number for a variable. It stays where you put it, regardless of ordering.
AutomaticLeave the address unset and variables are placed starting at register 0, in the order they appear. Automatic placement skips slots already taken by explicit assignments.

Automatic placement does not de-duplicate: if the same value appears twice in your content, it gets two separate slots. If two variables need to share one register, assign that address explicitly to both — the display reads one value and shows it twice, which is usually what you actually wanted.

Master mode: the polling table

When the panel polls a PLC itself, each polling entry is one of two directions.

DirectionMeaning
Read (03 / 04)Remote address range → local registers. The local address is the destination.
Write (06 / 16)Local registers → remote address range. The local address is the source.

The same local address field means destination on a read entry and source on a write entry. That asymmetry catches people out when editing an existing table. The polling interval is the gap between entries, so a full cycle takes interval × number of entries, not interval.